W1209 Temperature Controller

Introduction

ZL-W1209A is a cooling / heating temperature controller PCB with 0. 1℃ accuracy.

Specification

Power supply: 12V DC
Control range: -50 ~ 110℃
Resolution: 0.1℃
Absolute accuracy: 1% at 25℃
Accuracy after calibration: 0.1℃
Output: 5A, 250Vac (pure resistance load)
Sensor: NTC, 0.5 meters long
Working: -20 ~ 60℃, 5 ~ 90%RH without dew
Dimension: W48.5 x H40 (mm)
Installation holes: W40.5 x H32 (mm)
Display: 0.28 inches LED digits

Display

The display brightness will be reduced, if there no key operation for 10 seconds.

Display

---

LLL

HHH

888

Remark

High temperature warning

Sensor open

Sensor Short

Restoring to factory default settings

Operation

Set Set-Point

 

Press〖SET〗key to enter into the set status. The current set-point value displays.
Press〖+〗or〖-〗to set the value (keeping depressed can fast set).
Press〖SET〗to exit, and save the settings.
The status will exit, and the setting will be saved, if no key operation within 10 seconds.
Factory default setting is 28.0℃.

Set System Parameters

Keep〖SET〗depressed for 5 seconds to enter into parameter setting status.
Press〖+〗or〖-〗to select the parameter code (see parameter code table below).
Press〖SET〗to display the value of the code. Press〖+〗or〖-〗to set the value. Press〖SET〗to return to parameter code selection.
Keep〖SET〗depressed for 3 seconds to exit, and save the settings.
The status will exit, and the settings will be saved, if no key operation for 10 seconds.

Parameter Code Table
The display brightness will be reduced, if there no key operation for 10 seconds.

Code

Function

Range

Rmark

Factory Default

P0

Cooling/Heating mode

C/H

C: Cooling; H: Heating

C

P1

Hysteresis

  0.1~15.0℃

 

2.0℃

P2

Up limit for set-point

-50℃~110℃

 

110℃

P3

Low limit for set-point

-50℃~110℃

 

-50℃

P4

Calibration

  -7.0~+7.0℃

 

0.0℃

P5

Delay action after power supplied

0~10 minutes

 

0

P6

High temperature warning point

0~110℃/OFF

OFF: disable

OFF

Control
Cooling Control (P0 = C)
If Troom ≥ Set-point, the relay energized;
If Troom ≤ Set-point – P1, the relay de-energized.
Heating Control (P0 = H)
If Troom ≤ Set-point, the relay energized;
If Troom ≥ Set-point + P1, the relay de-energized.
Relay Delay Protection: After power supplied, the relay could be energized after P5.
Restore to Factory Default Settings 
Keep〖+〗or〖-〗depressed simultaneously, then supply power.
One second later, all settings will be restored to factory default values.
Attention
For ac/dc module as load, the rated current should be no more 1/10th of output specification under pure resistance;
For tungsten lamp as load, the rated current should be no more 1/15th of output specification under pure resistance:
For motor, the rate current should be no more 1/5th of output specification under pure resistance.
For example: if drive a 1100W tungsten lamp with 5A (pure resistance spec.) relay, the relay contactor will be burnt immediately.